Comments by "Spruce_Goose" (@spruce_goose5169) on "The Engineering Mindset"
channel.
-
4
-
3
-
2
-
2
-
2
-
2
-
2
-
2
-
2
-
2
-
1
-
1
-
1
-
1
-
1
-
@ke6gwf I agree with most everything you say until the end.
>"You seem to think that because one transformer is only wound with a single coil going "up" from the neutral, and another transformer has a coil going out from each side of the Neutral, that somehow that makes the Neutral different"
No that's not what I am saying, but I admit that saying they were 'out of phase' was not accurate, nor was it relevant or helpful to the discussion. All I meant was that If you graphed voltage (for example), with ground as reference (x-axis) the primary coil plot would be climbing while the secondary coil plot is falling IF the 'hot' (coil end of the secondary being graphed against the center tap) is on the same end as the Primary neutral. This is to be expected when ground is referenced off the end of one coil and the middle for the other. Sorry, probably not doing a good job explaining this in words and it's really an irrelevant aside.
>"any voltage changes, frequency changes, etc, created by the generator will directly show up at the house"
Yes I agree. But this STILL doesn't mean there is no form of isolation. The power is coupled via induction (and sometimes a bit of capacitance I believe) but not via a conductive path. Have you heard of the term 'isolation transformer.' Isolation transformers are usually purpose built to further protect against those capacitive couplings and what not, but any transformer offers some isolation in that the conductive path is eliminated under normal operating circumstances.
It sounds like you think that because the energy source is forever and always the PoCo generator (agreed) that the electrons will view the end of their circuit as the same. Can you expand on why you think this? Google isolation transformer before you do for contemplation.
The PoCo generator powers the transformer, that we agree on, but the circuit in a conductive sense is isolated to the secondary.
Consider a bike chain system but with multiple chains and gear connections. The chains are like the 'circuits': each link in a chain will return to it's own individual sprocket (akin to a transformer), even though the source of the power itself is input down the line at the peddles.
I suppose I will bring up Delta connections again. How do explain the fact that many primary transmission lines lack a neutral altogether?
Cheers, enjyoinh tjhe discussion.
*Edited a million times because I can't type or formulate cohesive thoughts the first time around.
1
-
1
-
1
-
1
-
1
-
1
-
@robertbrandywine We need to separate voltage and current in this discussion.
Current flows through the circuit, and so yes, the 'neutral' has just as much current as the 'hot.' (Unless we're talking the main feeder neutral, in which case it carries the difference between the legs).
Voltage, on the other hand, does not flow through the circuit, it exists between two points. Take that to heart. It very much needs two defined points, and where you measure those two points can change the reading even if current is constant. The voltage drops across the load.
The key bit here is that the 'neutral'— which should really just be called the 'grounded conductor'— is only not 'hot' because it is intentionally grounded. This clamps the voltage to earth potential, which happens to be pretty close to the potential you and I are at when standing on the earth, as we do.
So does the neutral have voltage? Well that's an incomplete question. Voltage between which points?
To ground? No, not really.
To the other 'hot' conductor? Yes should have about 120 volts.
But remember that the 'neutral' (or grounded conductor as preferred) is only NOT HOT if it is in direct and low impedance connection with the earthed portion of the system. If you disconnected a neutral wire from the panel and grabbed ahold of it, suddenly you are a load in the circuit and the 'neutral' is actually a hot because you've disconnected it's clamp to ground by disconnecting it from the panel.
1
-
1
-
1
-
You are right it will not trip the breaker, but no it won't electrocute you, assuming it's in tact. If its on the neutral side of the load, its close to 0V, and so the casing would be close to 0V. If everything is wired correctly and in proper working order, a grounded metal case essentially IS touching the neutral (not technically due to wire resistance, but it's pretty negligible).
If, on the other hand, the neutral was open, the situation is different, and you could very well get electrocuted (though the EGC would also have to be open in this case, or lack one altogether). In this situation, a 'neutral' faulting to the case would more technically be a hot fault, even if the wire doing it was white.
Takeaway: open neutrals are dangerous. Don't ever touch neutrals without instrument verification!
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1